Isolated Grounding Solution

PT. GlobalNine Indonesia

Did You Know

The bird is immune to the high voltage since it has single reference of potential and isolated from other reference of potential.

Solution

Single Reference Isolated Grounding System To build immunity to the Telco System f rom the lightning pulse.

PT. Globalnine Indonesia

Did You Know

Lightning current pulse is just 8/20uS

PT. Globalnine Indonesia

When lightning strikes, our grounding conductor react more as inductive reactance /impedance?

Effect caused by

Resistance

By R (Resistance) :

  • V = l x R
  • = l x R h o x U A
  • = 3000 x 0.01725 x 10/400
  • = l.2Volt

lmpendance

By XL (Inductive Reactance) :

  • v = Lxdl/df
  • = 11.57 uH x 3000 I 8uS
  • =4,300Volt

Solution

Since light ning characteristic creat es complexity in our grounding system, grounding conductor shall be LIGHTNING CONDITIONED, i.e:

  • As Stright as possible
  • Must not be surrounded by metallic closed path

Did You Know

Our metallic part or conductor will corrode, especially at out door connection

Solution

Exothermic welding as Free maintenance connection

PT. Globalnine Indonesia

Exothermic welding result has higher current capacity than the conductor

Did You Know

What is the effect?

Grounding conductor's impedance can be higher than equipment conductor, therefore lightning current flow easier to the equipment instead of to the dedicated grounding conductor. That means destruction to the equipment by lightning.

Solution

PT. Globalnine Indonesia

When lightning strikes, our grounding conductor react more as inductive reactance /impedance?